李茜等
摘要:变压器损耗在电力系统能量损耗中占有很大的比例,在电力系统可靠供电的前提下,合理选择变压器的运行方式,可以优化变压器的功率损耗,实现降损节能。首先分析了变压器功率损耗和运行效率的关系,然后根据不同的负载情况,计算变压器并列与分列运行的临界条件,最后讨论了实际运行中选择变压器运行方式应该考虑的因素,来实现变压器可靠、经济、高效的运行。
关键词:电力变压器;效率;经济运行
中图分类号:TM4 文献标识码:A 文章编号:1009-3044(2015)23-0141-04
Economical Operation of Power Transformer
LI Qian, HOU Liu-peng, TANG Wei, ZHAO Yan
(College of Electrical and Information Engineering,Shaanxi University of Science and Technology,Xian 710021, China)
Abstract: The power loss of transformer has a large proportion among that of power system.Under the premise of reliable power supply,reasonable choice of transformer operation mode can optimize the power loss of the transformer to achieve loss reduction and energy conservation.In this theses,the relationship between power loss and efficiency are analyzed and paralleled and disaggregate critical conditions are figured out aiming at various circumstances.Finally,some factors that should be taken into account when choosing its operation mode are discussed to assure transformer to operate reliably,economically and efficiently.
Key words: power transformer;efficiency;economical operation
随着国民经济的飞速增长,电力需求日益增加,电力网的作用日益突出。变压器作为电力系统运行的主要设备之一,由于它在电力系统中总台数多、总容量大,年均总电能损耗占发电量的10%以上,约占电力系统线损的50%。可见,变压器的运行效率直接影响到电力系统的成本和效益。因此,如何优化变压器的运行成为了实现电力网节能减排、优化利用资源的途径[1]。
变压器综合功率损耗是指变压器运行中有功功率损耗与因无功功率损耗使其受电网增加的有功功率损耗之和。通过计算变压器综合功率损耗,分析运行中的系统有功功率和无功功率增长情况,确定合适的变压器运行方式来实现电力系统的降损节能[2]。
1 变压器的优化指标
1.1 变压器的损耗
电力网的损耗包括有功功率损耗和无功功率损耗,其中变压器和输电线路的损耗占电力网损耗的大部分。变压器有功功率损耗分为铁损和铜损,铁损称为空载损失,是基本与负荷无关,认为是不变的,铜损与负荷电流的平方成正比,又称短路损失。变压器无功功率损耗由空载电流造成,它与铁芯有关而与负荷无关。变压器的综合功率损耗表达式为: